Pace Scientific Data Loggers and Sensors

[ Home | What's New | Products | Contact | International Distributors ]

WattHour Sensor

Connects directly to the XR5 Data Logger.  No external power required.


WNB-3Y-208 WattHour Sensor

Specifications - PACE WattHour Sensors
Accuracy ±0.5% of reading + CT error
Current Transformers 0 to 0.333 VAC
Operating Temperature -30 to 55°C (-22 to 131°F)

Power Line Frequency:

50 or 60 Hz

Operating Voltage Range:

-20%, +15% of nominal
Pulse Output 4 Hz at full scale power
Isolation, Pulse Output 5000 VAC
Connection, Pulse Output Detachable Screw Terminal Block
Connection, AC Voltage Detachable Screw Terminal Block
Connection, Current Transformers Detachable Screw Terminal Block
Overall size 3.3" x 5.6" x 1.5" (84 x 143 x 39 mm)

 

Pace Part No.

VAC

Line to Line

VAC

Line to Neutral

Maximum

Phases

Maximum

Wires

WNB-3Y-208 120 208-240 3 4
WNB-3Y-480 277 480 3 4
WNB-3Y-600 347 600 3 4
WNB-3D-240 230 208-240 3 3
WNB-3D-480 277 480 3 3

The following models have European voltage levels and CE marking.

WNB-3Y-400 230 400 3 4
WNB-3D-400 230 400 3 3

XR5 Data Logger

  XR5-SE User's Guide  

Placing an Order

Discontinued WH series WattHour Sensors Installation Guide [pdf file, 610kb]

Tel: (704) 799-0688 / Fax: (704) 799-0177 / e-mail: sales@pace-sci.com

[ Home | What's New | Products | Contact | International Distributors ]

Copyright © 2011 Pace Scientific Inc.
Last modified: June 02, 2011